LCD Display Duct Temperature And Humidity Transmitter 4-20mA
| Operating Humidity: | 0...100%RH | Temperature Range: | DIP Switch |
|---|---|---|---|
| Display: | Blacklight LCD | Temperature Range: | −35 ··· +80 °C |
| Temperature-accuracy: | ±0.3°C (20-60°C) | Humidity Range: | 0 ··· 100 %RH |
| Humidity-accuracy: | ±2% (0-90% @25°C) / ±3% (90-100% @25°C) | Output: | 4-20mA/0-5V/0-10V/RS-485 |
| Operating Temperature: | -35 ··· +70°C | ||
| Highlight |
Duct Temperature And Humidity Transmitter,CE Temperature And Humidity Transmitter,M20 Temp Humidity Transmitter |
||
4-20mA LCD display duct temperature temperature and humidity transmitter
Description
The humidity sensor is unsealed. In order to protect the accuracy and stability of the measurement, it should be avoided to use in the atmosphere of acid, alkali and organic solvent. Also avoid using in dusty environment. In order to correctly reflect the humidity of the space to be measured, it is also necessary to avoid placing the sensor in a dead corner that is too close to the wall or has no air circulation. If the measured room is too large, multiple sensors should be placed.
Feature
- LCD display
Large size backlight display
- Shell connected by hinge
More convenient wiring and setting
- M16 M20 double cable gland
Cable size φ5…12mm
- Smooth and flflat surface
Prevent the pollution of the shell surface in harsh environment
- IP65/NEMA4
Application
- HVAC system
- Greenhouse
- Food transportation
- Cold storage and refrigeration
- Clean room environment monitoring
Technical Data
| Model | KTH500 |
| Power Supply | 16-30VDC(2wire 4-20mA)/16-30V AC or V DC (0-5V/0-10V/4-20mA/RS-485 ) |
| Output | 4-20mA/0-5V/0-10V/RS-485 |
| Operating Temperature | -30…+70℃ |
| Storage Temperature | -40…+60℃ |
| Operating Humidity | 0...100%RH |
| Temperature Range | DIP Switch |
| Display | LCD |
| Maximum Wind/Flow Speed | 30m/s |
| Electromagnetic compliance | EN61326-1,Industrial Environment |
| Housing Material | PC&ABS,UL94V-0 |
| Protection Class | IP65/NEMA 4 |
| Cable Gland | M16*1.5 |
| Measurement Performance-Temperature | |
| Measurement Range | -35...+80℃ |
| Accuracy | ±0.3℃(20-60℃) |
| Temperature Dependence | ±0.01℃/℃ |
| Measurement Performance-Humidity | |
| Measurement Range | 0...100%RH |
| Accuracy | ±2%(0-90% @25℃)/±3%(90-100%@25℃) |
| Stability in Typical HVAC Applications | ±0.01RH/Year |
Dimension(mm)


Measuring range adjustment

Ordering guide
KTH500——Output——Installation——Filter
| Model | Output | Installation | Filter | |||
| KTH500 | 4-20mA(2 wire) | (E) | Wall | (W) | PTFE | (P) |
| 4-20mA(3 wire) | (F) | Duct | (D) | Stainless | (S) | |
| 0-5V/0-10VAD(3 wire) | (G) | |||||
| RS-485 | (H) | |||||